Pump Groups
TECHNICAL DATA
Voltage
230 VAC 50/60 Hz
Power consumption
10-75 W, depending on pump
speed
Max. working pres-
sure
1.0 MPa (10 bar)
Working tempera-
ture
Min. 5 °C/Max. 95 °C
Ambient tempera-
ture
Min. 5 °C/Max. 58 °C
Thread standard
Rp - female thread,
G - male thread
Media
Water - Glycol mixture max. 50%
Circulating pump
Wilo Para 15-130/8-75/SC-9,
Wilo Para 25-180/6-43/SC-12,
Wilo Para 25-180/8-75/SC-12,
Wilo Para zKu 15-130/8 SC
Material valve body
Brass EN 12165 CW617N
Material insulation
Expanded Polypropylene EPP
LK HydronicGroup is a complete pump group that is suitable
for heating where direct supply or mixed supply is desirable.
Consists of a highly efficient circulation pump, insulation, wall
mounting bracket and two ball valves with thermometer, on the
return side there is an integrated check valve.
LK 860 manifold available with or without hydraulic separator
for one, two, three, four and five pump groups. Wall mounting
bracket are included with the manifold.
LK 861 pump group where direct supply is desired.
LK 862 pump group where mixed supply is desired, a three-way
mixing valve is included.
LK 863 pump group where mixed supply is desired, a thermic
mixing valve is included. The LK 551 HydroMix has a thermo-
static element that regulates the supply and return to achieve
the desired supply temperature.
LK HydronicGroup C/C 125
• All in one
• Easy to install
• Easy to combine with electronic
regulation
-LK 864 pump group with a thermic loading valve LK 823 Ther-
moVar®. The pump group is intended to ensure both an optimal
temperature stratification in the storge tank and high return tem-
perature to the boiler, thus increasing the efficiency of the system.
LK 865 is a complete unit for hot water circulation. Consists of
a mixing valve, cross, circulation pump, insulation, connection
kit and three check valves. The LK 551 HydroMix mixing valve
has a thermostatic element that regulates the supply of both
cold and hot water to the desired temperature. The valve has an
anti-scald function that closes for incoming hot water if the cold
water supply ceases.
LK 866 is a pump group with a four way mixing valve, LK 841
ThermoMix®. The pumpgroup is designed for heating systems
where a high return temperature is required to prevent corro-
sion and thus extend the life length of the heat source.
LK 867 is a pump group with a four way mixing valve, LK 830
ThermoMix® B. The pump group has a 4-way bivalent mixing
valve that is designed for heating systems, where energy is
taken from two heating units connected in series or parallel or
for storage tank systems where energy is extracted from two
levels. The pump group should be equipped with an automatic
control unit to ensure that the most favourable heat source is
prioritised at all times.
LK 861 - Pump group where direct supply is desired.
9