PRESTAZIONI LINEA BOLLITORI
47
MODELLO
2000 l/h
14
60 °C
2000 l/h
23
70 °C
2000 l/h
29
80° C
2000 l/h
17
70 °C
2000 l/h
22
80° C
OMEGA 750
SCAMBIATORI FISSI ACQUA TECNICA
INFERIORE
2,4 m2
MANDATA (NELLO SCAMBIATORE)
PORTATA
ΔT
T
Prelievo ACS in continuo
10-45 °C
35 ΔT
POTENZA
PORTATA
34 kW
0,23 l/s
826 l/h
53 kW
0,36 l/s
1307 l/h
67 kW
0,46 l/s
1651 l/h
SUPERIORE
1,8 m2
MANDATA (NELLO SCAMBIATORE)
PORTATA
ΔT
T
2000 l/h
11
60 °C
Prelievo ACS in continuo
10-45 °C
35 ΔT
POTENZA
PORTATA
25 kW
0,17 l/s
619 l/h
40 kW
0,27 l/s
980 l/h
50 kW
0,34 l/s
1238 l/h
PERDITE DI CARICO SCAMBIATORI FISSI ACQUA TECNICA
500
450
400
350
300
250
200
150
100
50
0
2,4 m2
1,8 m2
0
500
1000
1500
2000
2500
3000
Portata [l/h]
3500
4000
4500
5000
[
m
b
a
r
]
PRELIEVO ACS
ACCUMULO RISCALDATO SOLO NELLA PARTE INFERIORE
T acc.
45 °C
T prim.
10 °C
T prim.
T acc.
ACS PRELEVABILE [lt]
10 min
60 min
55 °C
50 °C
962
1485
65 °C
60 °C
1280
2070
70 °C
60 °C
1334
2280
80 °C
60 °C
1395
2550
PRELIEVO ACS
ACCUMULO RISCALDATO SOLO NELLA PARTE SUPERIORE
T acc.
45 °C
T prim.
T prim.
T acc.
ACS PRELEVABILE [lt]
10 min
60 min
55 °C
50 °C
362
708
65 °C
60 °C
470
894
70 °C
60 °C
501
1116
80 °C
60 °C
540
1338
10 °C
BOLLITORI, SERBATOI E CELLE TERMICHE 2023
www.dynergysrl.it