TECHNICAL DATA
Angle of rotation
60°/360°
Leakage
Leakage Solar:
< 0.1% of Kvs at 100 kPa
< 0.5% of Kvs at 100 kPa
Operation time
8 seconds (60°)
Max. working pressure
1.0 MPa (10 bar)
Max. differential pressure
100 kPa (1 bar)
Working temperature
Art.no. 066399, 066418:
Cooling/Heating (inkl.
adapter):
Min. 5 °C/Max. 80 °C (90 °C briefly)
Min. 5 °C/Max. 70 °C (80 °C briefly)
Min. -15 °C/Max. 120 °C (160 °C
briefly)
Ambient temperature
Min. 1 °C/Max. 60 °C
Thread standard
Rp - female thread,
G - male thread, ISO 228/1
Protection type
IP 40 (Molex®) / IP 44 (Cable)
Media
Water - Glycol mixture max. 50%
Ethanol mixture max. 30%
Electrical connection
Fixed wire alternatively Molex®
or Molex®-compatible connector,
6-circuit
Signal connector
Single pole SPST
Cable specification
Dimension 3 x 0.75 mm2
Wire colours
Blue, brown, black
External insulation
PVC
Actuator
7 VA, 230 VAC, 50 Hz
7 VA, 24 VAC, 50 Hz
Material valve body
Brass EN 12165 CW617N
Material external cover
Brass EN 12164 CW614N
Material slide/spindle
PPS Composite
Type approval certificate
CE (Actuator only)
Zone Valve
LK 525 MultiZone 3W
• Turning slide to reduce risk of stalling
• Minimal internal leakage
• Quick and easy assembly with clip system
13
8.0
WIRING DIAGRAM
Open
Closed
B
B
A
A
Closed
Open
CAPACITY DIAGRAM
100.0
10.0
1.0
0.1
Kvs (m3/h)
LK 525 MultiZone 3W is a motorized 3-way zone valve for On/
Off control. The zone valve is designed with a turning slide which
allows it to withstand a larger pressure difference and reduces
the risk of it stalling after a long intermission. This makes it
especially suited for heat pump applications where there can
be long intermissions between the changes to the direction of
the flow during the warm season. On the upper surface of the
actuator is an indicator that shows which port is open.
Installing the 066177 plastic adapter between the valve unit and
the motor protects the motor against condensation, icing and
high temperatures.
The zone valve must not be installed with the motor underneath
the valve unit.
In case of a power failure, the valve cone stays in its current po-
sition. When the power is switched off, the valve can be manual-
ly set to the centre position, which distributes the flow between
the heating and tap water circuits. Remove the motor and turn
the spindle about 30° or turn until hot water flows through both
valve ports. When the power is restored, turn the valve back to
its original position and reinstall the motor.
Please note that the motor can be installed in only one position.
0.1
1.0
10.0
Pressure Drop (kPa)
100.0
7.0