Flow Adjustment Valve
LK 435 OptiFlow
• With MemoStop for locking setting
• Adjusted with Allen key while reading off flow
on a clear scale
TECHNICAL DATA
Max. working pressure
1.0 MPa (10 bar)
Max. differential pressure
100 kPa (1,0 bar)
Working temperature
Water/Glycol 50/50%
Water/Ethanol 70/30%
Min. -20 °C / Max. 80 °C
(90 °C briefly)
Min. -20 °C / Max. 70 °C
(85 °C briefly)
Media
Water - Glycol mixture max. 50%
Ethanol mixture max. 30%
Material valve body
Nickel-plated Brass EN 12165
CW617N
Measure accuracy
Flow meter: +/- 12%
Flow ranges
2-16 l/min, 4-36 l/min
Thread standard
Adjustment valve inlet: M - male
Adjustment valve outlet: F - female
VALVE CHARACTERISTICS
LK 435 OptiFlow is a group valve for flow adjustment of
hydraulic systems such as underfloor heating, traditional
heating and cooling systems. Adjustments are easily made us-
ing an Allen key. No measuring equipment is needed. The flow
rate is read off directly from the visual flow indicator. The flow
meter continuously measures and displays the actual flow rate
during operation.
LK 435 OptiFlow has a MemoStop function for locking the
setting. This means that the valve can be used as a shut-off
valve without losing settings. A marking plate for labelling and
documenting the setting is enclosed. LK 435 OptiFlow can be
supplemented with a thermometer and threaded union parts,
straight or angular, with rotating nut for simple assembly to, for
example, an LK 430 Manifold RF - see under Accessories. The
thermometer is placed in the valve’s integrated sensor pocket.
The valve can be mounted in any position. The arrow on the valve
body indicates the flow direction. For accurate measurement
a straight piece of tube at least of the same length as the valve
body should precede the balancing valve. When assembling to
an LK 430 Manifold RF the adjustment valve can be fitted direct-
ly to the manifold, thus replacing the shut-off valve.
The flow meter is designed so that the fluid does not flow through
the glass in order to protect it from debris and dirt. However, after
a period of time the glass may still have to be cleaned as the fluid
often becomes contaminated and blackened. It is then easy to
remove the glass to clean it. The function/setting of the valve is
not affected by deposits in the glass.
WITH LK 430 MANIFOLD RF
6.0
5.0
4.0
3.0
K
v
(
m
3
/
h
)
2.0
1.0
0.0
OptiFlow 216 (Kvs 3.5)
OptiFlow 436 (Kvs 4.5)
0
1
2
3
4
5
6
7
Number of turns
161