LINEA Y NEXT STAGE / PUHY-P Y(S)NW-A1
MODELLO
HP
Moduli
Alimentazione
Raffreddamento
Riscaldamento
Livelli Sonori *
4
Connettività
Diametro
tubazioni
refrigerante
Ventilatore
Compressore
Dimensioni
esterne
Peso netto
Refrigerante
PUHY-P800YSNW-A1(-BS)
PUHY-P850YSNW-A1(-BS)
PUHY-P900YSNW-A1(-BS)
PUHY-P950YSNW-A1(-BS)
PUHY-P1000YSNW-A1(-BS)
32
34
36
38
40
PUHY-P(350+450)YNW-A1
PUHY-P(400+450)YNW-A1
Capacità nominale *
1
Potenzaassorbita
kW
26,31
30,0
30,42
30,0
33,13
EER
SEER
Campo operativo
di temperatura
3,42
6,48
+15~+24
-5~+52
90,0/100,0
20,97/24,87
4,29/4,02
3,88
+15~+27
-20~+15,5
67,5/71 (85/90)
50-130%
P10-P250/2-50
19,05
34,93
Propeller fan x 4
1858(1798)x1240x740
1858(1798)x1240x740
1858(1798)x1240x740
mm
1858(1798)x1240x740
1858(1798)x1240x740
1858(1798)x1240x740
Capacità nominale*
2
/
Capacità nominale massima*
3
Potenza assorbita /
Potenza assorbita max.
COP/COP max
SCOP
Campo operativo
di temperatura
Interno
Esterno
Pressione Sonora (Potenza sonora)
Capacità totale
Modello/Quantità
Liquido
Gas
CITY MULTI
Interno
Esterno
3,41
6,59
+15~+24
-5~+52
113,0/127,0
25,91/31,05
4,36/4,09
4,06
+15~+27
-20~+15,5
68/69,5 (85/88)
50-130%
P10-P250/2-50
19,05
41,28
Propeller fan x 5
V/Hz/n°
kW
°C BU
°C BS
kW
kW
°C BS
°C BU
dB(A)
mm
mm
PUHY-P(450+450)YNW-A1 PUHY-P (250+350+350)YNW-A1 PUHY-P (250+350+400)YNW-A1
3-fase 380-415V 50Hz
90
96,0
101,0
108,0
113,0
3,20
6,38
+15~+24
-5~+52
96,0/108,0
23,07/27,76
4,16/3,89
3,86
+15~+27
-20~+15,5
68,5/71,5 (86/91)
50-130%
P10-P250/2-50
19,05
41,28
Propeller fan x 4
3,32
6,41
+15~+24
-5~+52
101,0/113,0
24,33/29,12
4,15/3,88
3,71
+15~+27
-20~+15,5
68,5/72,5 (87/92)
50-130%
P10-P250/2-50
19,05
41,28
Propeller fan x 4
3,60
6,72
+15~+24
-5~+52
108,0/119,5
24,10/28,38
4,48/4,21
4,09
+15~+27
-20~+15,5
66/68 (84/87)
50-130%
P10-P250/2-50
19,05
41,28
Propeller fan x 5
1858(1798)x920x740
1858(1798)x920x740
1858(1798)x1240x740
1858(1798)x1240x740
1858(1798)x1240x740
1858(1798)x1240x740
Tipo x quantità
Portataaria
m
3
/min
270+305
300+305
305+305
185+270+270
185+270+300
Tipo
Scroll ermetico inverter
Resamotore
kW
8,6+11,7
11,4+11,7
11,7+11,7
5,3+8,6+8,6
5,3+8,6+11,4
A(A*
5
)xLxP
kg
277+293
277+293
293+293
CaricaR410A
kg
20,6
20,6
21,6
26,1
26,1
CO2eq.*
6
Tons
43,01
43,01
45,10
54,49
54,49
MODELLO
HP
Moduli
Alimentazione
Raffreddamento
Riscaldamento
Livelli Sonori *
4
Connettività
Diametro
tubazioni
refrigerante
Ventilatore
Compressore
Dimensioni
esterne
Peso netto
Refrigerante
V/Hz/n°
kW
°C BU
°C BS
kW
kW
°C BS
°C BU
dB(A)
mm
mm
PUHY-P1050YSNW-A1(-BS)
PUHY-P1100YSNW-A1(-BS)
PUHY-P1150YSNW-A1(-BS)
PUHY-P1200YSNW-A1(-BS)
PUHY-P1250YSNW-A1(-BS)
42
44
46
48
50
PUHY-P (250+400+400)YNW-A1 PUHY-P (350+350+400)YNW-A1 PUHY-P (350+400+400)YNW-A1 PUHY-P (400+400+400)YNW-A1 PUHY-P (400+400+450)YNW-A1
3-fase 380-415V 50Hz
Capacità nominale *
1
Potenzaassorbita
kW
36,41
36,79
40,49
44,29
44,30
EER
SEER
Campo operativo
di temperatura
Interno
Esterno
3,24
6,47
+15~+24
-5~+52
118,0/132,0
27,76/33,08
4,25/3,99
4,05
+15~+27
-20~+15,5
68,5/70,5 (86/90)
50-130%
P10-P250/3-50
19,05
41,28
Propeller fan x 5
1858(1798)x920x740
mm
1858(1798)x1240x740
1858(1798)x1240x740
3,37
6,49
+15~+24
-5~+52
124,0/140,0
28,44/34,22
4,36/4,09
4,07
+15~+27
-20~+15,5
68,5/70 (86/89)
50-130%
P10-P250/3-50
19,05
41,28
Propeller fan x 6
1858(1798)x1240x740
1858(1798)x1240x740
1858(1798)x1240x740
3,21
6,38
+15~+24
-5~+52
130,0/145,0
30,51/36,25
4,26/4,00
4,03
+15~+27
-20~+15,5
69/71 (86/90)
50-130%
P10-P250/3-50
19,05
41,28
Propeller fan x 6
1858(1798)x1240x740
1858(1798)x1240x740
1858(1798)x1240x740
3,07
6,29
+15~+24
-5~+52
136,0/150,0
32,61/38,36
4,17/3,91
4,01
+15~+27
-20~+15,5
70/72 (87/91)
50-130%
P10-P250/3-50
19,05
41,28
Propeller fan x 6
1858(1798)x1240x740
1858(1798)x1240x740
1858(1798)x1240x740
3,16
6,30
+15~+24
-5~+52
140,0/156,5
33,65/40,12
4,16/3,90
3,91
+15~+27
-20~+15,5
70/73 (88/92)
50-130%
P10-P250/3-50
19,05
41,28
Propeller fan x 6
1858(1798)x1240x740
1858(1798)x1240x740
1858(1798)x1240x740
Capacità nominale*
2
/
Capacità nominale massima*
3
Potenza assorbita /
Potenza assorbita max.
COP/COP max
SCOP
Campo operativo
di temperatura
Interno
Esterno
Pressione Sonora (Potenza sonora)
Capacità totale
Modello/Quantità
Liquido
Gas
CITY MULTI
118,0
124,0
130,0
136,0
140,0
Tipo x quantità
Portataaria
m
3
/min
185+300+300
270+270+300
270+300+300
300+300+300
300+300+305
Tipo
Scroll ermetico inverter
Resamotore
kW
5,3+11,4+11,4
8,6+8,6+11,4
8,6+11,4+11,4
11,4+11,4+11,4
11,4+11,4+11,7
A(A*
5
)xLxP
kg
213+277+277
CaricaR410A
kg
26,1
29,4
29,4
29,4
30,4
CO2eq.*
6
Tons
54,49
61,38
61,38
61,38
63,47
*
1
*
2
*
3
Condizioni nominali:
Riscaldamento : Interno 20°C BS. Esterno 7°C BS / 6°C BU. Lunghezza tubi 7.5 m, differenza livello 0 m.
Raffreddamento Interno 27°C BS / 19°C BU. Esterno 35°C BS. Lunghezza tubi 7.5 m, differenza livello 0 m.
*
2
Capacità nominale ( registrata Eurovent - Conto Termico e Detrazioni)
*
4
Valori misurati in camera anecoica. Raffreddamento-Riscaldamento
*
5
senza piedini di sostegno
*
6
GWP di HFC R410A pari a 2088 secondo regolamento 517 / 2014
I dati di SEER e SCOP sono basati in conformità allo standard di misura EN14825
56
277+277+277
277+277+277
277+277+277
277+277+293
213+277+277
213+277+277