Info display
The controller checks the status
of the plants and indicates errors.
This is a plausibility check of the
entries and is used for informa-
tional purposes in the event of
malfunctions.
Info code
Description
Possible cause
54
Thermal disinfection, temperature
not reached or not carried out.
n Primary temperature is too low.
n Tapping is in progress.
n No circulation flow or circula-
tion flow rate too low.
57
Maximum temperature for circula-
tion ZIR02 MAX TEMP CIRCULATION
exceeded.
253
Master not in sequence, eBUS
address of master not entered in
STN1 (04:022).
Incorrect basic setting
n STN1 (04:022) = 0
298
Lower switching threshold is set
lower than the minimum pump
speed.
Incorrect basic setting
n KAS05 (36:021) < STE01
(05-090)
318
Fresh water setpoint temperature
legionella protection temperature.
Incorrect basic setting
n BAS01 (05:051) > LEG01
(05:004).
321
Minimum temperature loss
imum temperature loss.
Incorrect basic setting
n STE12 (05:100) > STE14
(05-101).
322
Minimum tapping volume
imum tapping volume.
Incorrect basic setting
n STE13 (05:102) > STE15
(05:103).
E
ERROR
Total fault message
F
FRIWA
Primary pumps
H
h
Hours
I