LINEA SISTEMI HVRF Y / SPECIFICH
E
2 0 2 1
COMPLIAN
T
MODELLO
PUHY-M400YNW-A1(-BS)
PUHY-M450YNW-A1(-BS)
PUHY-M500YNW-A1(-BS)
HP
16
18
20
Alimentazione
Tensione/Freq./Fasi
V/Hz/n°
3-phase 4-wire 380-400-415 V 50/60 Hz
Capacità nominale*1
kW
45
50
56
Potenza assorbita
kW
14,65
14,70
17,7
2
Raffreddament
o
EER*
kW
3,07
3,40
3,16
Camp
o
operativ
o
di temperatur
a
Interna BU
Esterna BS
°C
15,0~24,0
15,0~24,0
15,0~24,0
°C
-5,0~52,0
-5,0~52,0
-5,0~52,
0
Capacità nominale*2
kW
50
56
63
Potenza assorbita
kW
13,69
16
17.07
Riscaldamento
COP*
kW
3,65
3,50
3,69
Campo ope-
rativo
di temperatur
a
Interna BS
°C
15,0~27,0
15,0~27,0
15,0~27,0
Esterna BU
°C
-20,0~15,5
-20,0~15,5
-20,0~15,5
Livello di pression
e
82.5 / 86.0
65.5 / 69.5
83.5 / 88.5
63.5 / 66.
5
82 / 85.
5
Unità int. collegabili
Modello
/
Quantità
W10~125,WL10~50/2~50
W10~125, WL10~50/2~50
W10~125, WL10~50/2~5
0
Ø est. attacchi refr.
mm
12,7/28,58
15,88/28,58
15,88/28,5
8
Dimensioni esterne **
(AxLxP)
mm
1858 x 1240 x 740
1858 x 1240 x 740
1858 x 1750 x 74
0
Peso netto
kg
273
290
329
Carica refr. R32/CO2 Eq*4
9,8/6,62
10,8/7,29
10,8/7,29
kg/Tons
*1 Condizioni di raffreddamento nominali: Interno 27°C BS / 19°C BU. Esterno 35°C BS. Lunghezza tubi 7.5 m, differenza livello 0 m. (soggetto a JIS B8615-2
)
*2 Condizioni di riscaldamento nominali: Interno 20°C BS. Esterno 7°C BS / 6°C BU. Lunghezza tubi 7.5 m, differenza livello 0 m. (soggetto a JIS B8615-2
)
*3 Valori misurati in camera anecoica. Raffreddamento/Riscaldament
o
*4 GWP del gas R32 pari a 675 secondo Regolamento 517 / 2014
*
I coefficienti prestazionali COP e EER sono prestazioni di sistema e come tali non si riferiscono solo alla unità esterna bensì sono comprensivi sia dei coefficienti di produzione dell’acqua (Unità esterna+Unità Idronica
)
che dei coefficienti di distribuzione dell’acqua (Unità Idronica + Unità interne).
** Senza piedi di sostegno rimovibili, A=1798 mm.
37