TACOCONTROL Z1 S

Faults

The error message also indicates the priority level of

the error. Depending on the priority level, the unit is

switched off:

– Critical (A) = unit is switched off, because there

is an error that is critical for the installation.

– Low (B) = parts of the unit are switched off.

– Warning (C) = unit continues operating.

9.3.2 Fault table

Faults with error message

The following sections describe faults and work required to repair

them, which are displayed on the HMI.

Fault description

Cause

Remedy

Personnel

01 Supply temperature: noSensor

Signal fault on the heat network supply

temperature sensor.

Valves are closed, circulation pump is off.

Sensor incorrect or

not connected.

Check the wiring and

reconnect the sensor,

if necessary.

Electrician

Heating and

sanitary techni-

cian

Sensor defective.

Replace the sensor.

Electrician

Heating and

sanitary techni-

cian

10 Supply temperature too high: Active

Temperature of the heat network supply

higher than the defined maximum value.

DHW valve is closed.

Water temperature in

the supply is higher

than allowed.

Check the heat supply.

Heating and

sanitary techni-

cian

20 DHW temperature; no Sensor

Signal fault on the domestic hot water

sensor.

DHW valve is closed.

Sensor incorrect or

not connected.

Check the wiring and

reconnect the sensor,

if necessary.

Electrician

Heating and

sanitary techni-

cian

Sensor defective.

Replace the sensor.

Electrician

Heating and

sanitary techni-

cian

21 DHW temperature too high: Active

Temperature of the domestic hot water

higher than the defined maximum value.

Control valve defec-

tive.

Replace the control

valve.

Heating and

sanitary techni-

cian

A setpoint that is too

high has been saved.

Correct the setpoint.

Heating and

sanitary techni-

cian

30 DHW setpoint reduction: Active

Setpoint reduction for domestic hot water is

active.

Temperature of

supply heat network

insufficient for the

setpoint saved.

Increase the tempera-

ture of the supply heat

network.

Reduce the nominal

temperature for the

domestic hot water.

Heating and

sanitary techni-

cian