PREMANT district heating pipe

Concrete block for

fixed point

For maximum fixed point forces

PRE 6.515

d

mm

26.9

33.7

42.4

48.3

60.3

76.1

88.9

114.3

139.7

168.3

219.1

273.0

323.9

355.6

406.4

457.2

508.0

Concrete block dimensions

A1

A

L*

Calculation basis for the size of the concrete block

a

B

L*

L* max. width

For divergent fixed point forces and soil conditions, the foundation dimensions must be calculated.

Steel pipe

DN

20

25

32

40

50

65

80

100

125

150

200

250

300

350

400

450

500

Fixed point force

Fsmax

B

kN

m

66.5

0.8

83.7

0.8

107.2

1.0

123.1

1.0

172.4

1.2

219.9

1.4

284.1

1.6

412.9

2.0

507.6

2.2

680.9

2.5

1000.6

3.0

1388.5

3.5

1847.0

4.2

2052.0

4.5

2592.0

5.2

2920.0

5.6

3240.0

5.6

Pipe distance

a

mm

270

270

280

280

295

320

340

390

415

450

550

680

745

810

890

890

980

• Max.thrustfor2pipes:Fsmax=2·As·dT,[dT=165N/mm2,∆T=70°K]

• Coverage height H = 0.8 m

• Foundation dimensions are based on a frictional angle of  = 32.5° for friable soils (coefficient of friction m = 0.40)

• Apparent density g = 18 kN/m3

• Ground specification acc. DVGW GW 310

Concrete quality

• P 350 to DIN 1045, impermeable to water with armouring

17.1.2025 BGP

Subject to technical changes

m

m

m

0.40

0.8

0.8

0.40

0.8

0.8

0.40

0.8

0.8

0.45

0.9

0.8

0.55

1.1

1.0

0.65

1.2

1.0

0.80

1.3

1.0

0.95

1.6

1.0

1.15

1.7

1.0

1.40

2.0

1.3

1.70

2.4

1.3

2.10

2.9

1.3

2.25

3.2

1.5

2.40

3.3

1.5

2.40

3.5

1.8

2.60

3.6

2.0

2.60

3.8

2.0

A

A

1

H