Fault description
Cause
Remedy
Personnel
No hot water at the
taps.
Ball valves are closed.
Open the ball valves.
Operator
Primary energy supply is
not reliable.
Check whether there is hot water at the
heat exchanger. If there is no hot water
at the heat exchanger, check the central
heating.
Operator
Heat exchanger is defec-
tive.
Replace the heat exchanger (
Ä Chapter
11.3 ‘Replacing the heat exchanger’
on page 54).
Heating and
sanitary techni-
cian
Primary circulation pump
defective.
Replace the primary circulation pump
(
Ä Chapter 11.4 ‘Replacing the pump’
on page 54).
Heating and
sanitary techni-
cian
Backflow preventer defec-
tive.
Replace the backflow preventer
(
Ä Chapter 11.5 ‘Replacing the backflow
preventer’ on page 55).
Heating and
sanitary techni-
cian
Controller defective or
power supply discon-
nected.
Check the power supply (
Ä Chapter 1.2
‘Other applicable documents’ on page 8).
Electrician
Insufficient hot
water at peak times.
Temperature sensor or
flow rate sensor defective.
Replace the temperature sensor or flow
rate sensor (
Ä Chapter 11.7 ‘Replacing
the temperature sensor’ on page 57,
Ä Chapter 11.6 ‘Replacing the flow rate
sensor’ on page 56).
Heating and
sanitary techni-
cian
Black water at the
taps.
Heat exchanger is defec-
tive or cold water supply is
contaminated.
Replace the heat exchanger (
Ä Chapter
11.3 ‘Replacing the heat exchanger’
on page 54).
Check the water quality.
Heating and
sanitary techni-
cian
Insufficient water
pressure at the taps.
Calcified water tap at the
taps.
Unscrew the water tap and decalcify.
Operator
Calcified pipes in the heat
interface unit or in the
entire pipe system.
Check the water quality and, if neces-
sary, take appropriate measures to
comply with country-specific regulations
regarding water quality.
Heating and
sanitary techni-
cian
Safety valve blows
off.
Pressure or temperature
on DCW/DHW or secondary
heating are too high.
Check the temperature or pressure and,
if necessary, regulate it.
Heating and
sanitary techni-
cian
Safety valve defective.
Check the network pressure and, if
necessary, replace the safety valve.
Heating and
sanitary techni-
cian
No heat transfer
despite open control
valve and demand
by the controller.
Dirty heat exchanger due
to incorrect flushing and
unclean heating water.
Flushing or replacing the heat
exchanger.
Heating and
sanitary techni-
cian
V03 06/2025 Item no. 215250 EA no. 1292