PRESTAZIONI LINEA BOLLITORI

49

MODELLO

2000 l/h

22

60 °C

2000 l/h

34

70 °C

2000 l/h

43

80° C

2000 l/h

29

70 °C

2000 l/h

36

80° C

ACQUAPOWER 1500 R1

OMEGA 1500

ACQUAPOWER 1500 R2

SCAMBIATORI FISSI ACQUA TECNICA

INFERIORE

3,6 m2

MANDATA (NELLO SCAMBIATORE)

PORTATA

ΔT

T

Prelievo ACS in continuo

10-45 °C

35 ΔT

POTENZA

PORTATA

50 kW

0,34 l/s

1238 l/h

80 kW

0,54 l/s

1961 l/h

101 kW

0,69 l/s

2477 l/h

SUPERIORE

3,0 m2

MANDATA (NELLO SCAMBIATORE)

PORTATA

ΔT

T

2000 l/h

18

60 °C

Prelievo ACS in continuo

10-45 °C

35 ΔT

POTENZA

PORTATA

42 kW

0,29 l/s

1032 l/h

67 kW

0,45 l/s

1634 l/h

84 kW

0,57 l/s

2064 l/h

PERDITE DI CARICO SCAMBIATORI FISSI ACQUA TECNICA

800

700

600

500

400

300

200

100

0

3,6 m2

3,0 m2

0

500

1000

1500

2000

2500

3000

Portata [l/h]

3500

4000

4500

5000

[

m

b

a

r

]

PRELIEVO ACS

ACCUMULO RISCALDATO SOLO NELLA PARTE INFERIORE

T acc.

45 °C

T prim.

10 °C

T prim.

T acc.

ACS PRELEVABILE [lt]

10 min

60 min

55 °C

50 °C

1911

2790

65 °C

60 °C

2523

3930

70 °C

60 °C

2619

4320

80 °C

60 °C

2730

4800

PRELIEVO ACS

ACCUMULO RISCALDATO SOLO NELLA PARTE SUPERIORE

T acc.

45 °C

T prim.

T prim.

T acc.

ACS PRELEVABILE [lt]

10 min

60 min

55 °C

50 °C

720

1380

65 °C

60 °C

930

1740

70 °C

60 °C

990

2160

80 °C

60 °C

1065

2580

10 °C

BOLLITORI, SERBATOI E CELLE TERMICHE 2023

www.dynergysrl.it