50

PRESTAZIONI LINEA BOLLITORI

MODELLO

2000 l/h

25

60 °C

2000 l/h

40

70 °C

2000 l/h

51

80° C

2000 l/h

29

70 °C

2000 l/h

36

80° C

ACQUAPOWER 2000 R1

OMEGA 2000

ACQUAPOWER 2000 R2

SCAMBIATORI FISSI ACQUA TECNICA

INFERIORE

4,2 m2

MANDATA (NELLO SCAMBIATORE)

PORTATA

ΔT

T

Prelievo ACS in continuo

10-45 °C

35 ΔT

POTENZA

PORTATA

59 kW

0,40 l/s

1445 l/h

93 kW

0,64 l/s

2288 l/h

118 kW

0,80 l/s

2890 l/h

SUPERIORE

3,0 m2

MANDATA (NELLO SCAMBIATORE)

PORTATA

ΔT

T

2000 l/h

18

60 °C

Prelievo ACS in continuo

10-45 °C

35 ΔT

POTENZA

PORTATA

42 kW

0,29 l/s

1032 l/h

67 kW

0,45 l/s

1634 l/h

84 kW

0,57 l/s

2064 l/h

PERDITE DI CARICO SCAMBIATORI FISSI ACQUA TECNICA

900

800

700

600

500

400

300

200

100

0

4,2 m2

3,0 m2

0

500

1000

1500

2000

2500

3000

Portata [l/h]

3500

4000

4500

5000

[

m

b

a

r

]

PRELIEVO ACS

ACCUMULO RISCALDATO SOLO NELLA PARTE INFERIORE

T acc.

45 °C

T prim.

10 °C

T prim.

T acc.

ACS PRELEVABILE [lt]

10 min

60 min

55 °C

50 °C

2542

3630

65 °C

60 °C

3346

5135

70 °C

60 °C

3468

5640

80 °C

60 °C

3610

6250

PRELIEVO ACS

ACCUMULO RISCALDATO SOLO NELLA PARTE SUPERIORE

T acc.

45 °C

T prim.

T prim.

T acc.

ACS PRELEVABILE [lt]

10 min

60 min

55 °C

50 °C

955

1780

65 °C

60 °C

1225

2240

70 °C

60 °C

1300

2760

80 °C

60 °C

1395

3280

10 °C

www.dynergysrl.it

BOLLITORI, SERBATOI E CELLE TERMICHE 2023