PRESTAZIONI LINEA BOLLITORI

55

PRELIEVO ACS

MODELLO

SCAMBIATORI FISSI ACQUA TECNICA

INFERIORE

7 m2

MANDATA (NELLO SCAMBIATORE)

PORTATA

ΔT

T

2000 l/h

42

60 °C

2000 l/h

67

70 °C

2000 l/h

84

80° C

MANDATA (NELLO SCAMBIATORE)

PORTATA

ΔT

T

2000 l/h

0

60 °C

2000 l/h

0

70 °C

2000 l/h

0

80° C

ACCUMULO RISCALDATO SOLO NELLA PARTE INFERIORE

HYDYRO1BT758000R1

Prelievo ACS in continuo

10-45 °C

35 ΔT

POTENZA

PORTATA

98 kW

0,67 l/s

2408 l/h

155 kW

1,06 l/s

3813 l/h

196 kW

1,34 l/s

4816 l/h

SUPERIORE

m2

Prelievo ACS in continuo

10-45 °C

35 ΔT

POTENZA

PORTATA

0 kW

0,00 l/s

0 l/h

0 kW

0,00 l/s

0 l/h

0 kW

0,00 l/s

0 l/h

PERDITE DI CARICO SCAMBIATORI FISSI ACQUA TECNICA

350

300

250

200

150

100

50

0

7 m2

l/h m2

0

500

1000

1500

2000

2500

3000

Portata [l/h]

3500

4000

4500

5000

[

m

b

a

r

]

T acc.

45 °C

T prim.

10 °C

T prim.

T acc.

ACS PRELEVABILE [lt]

10 min

60 min

55 °C

50 °C

1008

2175

65 °C

60 °C

1418

2875

70 °C

60 °C

1518

3200

80 °C

60 °C

1625

3700

PRELIEVO ACS

ACCUMULO RISCALDATO SOLO NELLA PARTE SUPERIORE

T acc.

45 °C

T prim.

T prim.

T acc.

ACS PRELEVABILE [lt]

10 min

60 min

55 °C

50 °C

0

0

65 °C

60 °C

0

0

70 °C

60 °C

0

0

80 °C

60 °C

0

0

10 °C

BOLLITORI, SERBATOI E CELLE TERMICHE 2023

www.dynergysrl.it