56
PRESTAZIONI LINEA BOLLITORI
MODELLO
2000 l/h
81
70 °C
2000 l/h
102
80° C
SUPERIORE
m2
MANDATA (NELLO SCAMBIATORE)
PORTATA
ΔT
T
2000 l/h
0
60 °C
2000 l/h
0
70 °C
2000 l/h
0
80° C
Y R1 1000
SCAMBIATORI FISSI ACQUA TECNICA
INFERIORE
8,5 m2
MANDATA (NELLO SCAMBIATORE)
PORTATA
ΔT
T
2000 l/h
51
60 °C
Prelievo ACS in continuo
10-45 °C
35 ΔT
POTENZA
PORTATA
119 kW
0,81 l/s
2924 l/h
188 kW
1,29 l/s
4630 l/h
238 kW
1,62 l/s
5848 l/h
Prelievo ACS in continuo
10-45 °C
35 ΔT
POTENZA
PORTATA
0 kW
0,00 l/s
0 l/h
0 kW
0,00 l/s
0 l/h
0 kW
0,00 l/s
0 l/h
PERDITE DI CARICO SCAMBIATORI FISSI ACQUA TECNICA
450
400
350
300
250
200
150
100
50
0
8,5 m2
l/h m2
0
500
1000
1500
2000
2500
3000
Portata [l/h]
3500
4000
4500
5000
[
m
b
a
r
]
PRELIEVO ACS
ACCUMULO RISCALDATO SOLO NELLA PARTE INFERIORE
T acc.
45 °C
T prim.
10 °C
T prim.
T acc.
ACS PRELEVABILE [lt]
10 min
60 min
55 °C
50 °C
1335
2775
65 °C
60 °C
1865
3688
70 °C
60 °C
1990
4100
80 °C
60 °C
2125
4725
PRELIEVO ACS
ACCUMULO RISCALDATO SOLO NELLA PARTE SUPERIORE
T acc.
45 °C
T prim.
T prim.
T acc.
ACS PRELEVABILE [lt]
10 min
60 min
55 °C
50 °C
0
0
65 °C
60 °C
0
0
70 °C
60 °C
0
0
80 °C
60 °C
0
0
10 °C
www.dynergysrl.it
BOLLITORI, SERBATOI E CELLE TERMICHE 2023