PRESTAZIONI LINEA BOLLITORI
57
PRELIEVO ACS
MODELLO
SCAMBIATORI FISSI ACQUA TECNICA
INFERIORE
1 m2
MANDATA (NELLO SCAMBIATORE)
PORTATA
ΔT
T
2000 l/h
6
60 °C
2000 l/h
10
70 °C
2000 l/h
12
80° C
MANDATA (NELLO SCAMBIATORE)
PORTATA
ΔT
T
2000 l/h
22
60 °C
2000 l/h
35
70 °C
2000 l/h
45
80° C
ACCUMULO RISCALDATO SOLO NELLA PARTE INFERIORE
Prelievo ACS in continuo
10-45 °C
35 ΔT
POTENZA
PORTATA
14 kW
0,10 l/s
344 l/h
22 kW
0,15 l/s
545 l/h
28 kW
0,19 l/s
688 l/h
SUPERIORE
3,7 m2
Prelievo ACS in continuo
10-45 °C
35 ΔT
POTENZA
PORTATA
52 kW
0,35 l/s
1273 l/h
82 kW
0,56 l/s
2015 l/h
104 kW
0,71 l/s
2546 l/h
PERDITE DI CARICO SCAMBIATORI FISSI ACQUA TECNICA
180
160
140
120
100
80
60
40
20
0
1 m2
3,7 m2
0
500
1000
1500
2000
2500
3000
Portata [l/h]
3500
4000
4500
5000
[
m
b
a
r
]
T acc.
45 °C
T prim.
10 °C
T prim.
T acc.
ACS PRELEVABILE [lt]
10 min
60 min
55 °C
50 °C
385
600
65 °C
60 °C
513
835
70 °C
60 °C
535
920
80 °C
60 °C
560
1030
PRELIEVO ACS
ACCUMULO RISCALDATO SOLO NELLA PARTE SUPERIORE
T acc.
45 °C
T prim.
T prim.
T acc.
ACS PRELEVABILE [lt]
10 min
60 min
55 °C
50 °C
160
462
65 °C
60 °C
233
596
70 °C
60 °C
260
804
80 °C
60 °C
291
1012
10 °C
BOLLITORI, SERBATOI E CELLE TERMICHE 2023
www.dynergysrl.it