58

PRESTAZIONI LINEA BOLLITORI

MODELLO

2000 l/h

14

70 °C

2000 l/h

18

80° C

SUPERIORE

4 m2

MANDATA (NELLO SCAMBIATORE)

PORTATA

ΔT

T

2000 l/h

24

60 °C

2000 l/h

38

70 °C

2000 l/h

48

80° C

HYDRO BT 400 R2

Y R2 400

SCAMBIATORI FISSI ACQUA TECNICA

INFERIORE

1,5 m2

MANDATA (NELLO SCAMBIATORE)

PORTATA

ΔT

T

2000 l/h

9

60 °C

Prelievo ACS in continuo

10-45 °C

35 ΔT

POTENZA

PORTATA

21 kW

0,14 l/s

516 l/h

33 kW

0,23 l/s

817 l/h

42 kW

0,29 l/s

1032 l/h

Prelievo ACS in continuo

10-45 °C

35 ΔT

POTENZA

PORTATA

56 kW

0,38 l/s

1376 l/h

89 kW

0,61 l/s

2179 l/h

112 kW

0,76 l/s

2752 l/h

PERDITE DI CARICO SCAMBIATORI FISSI ACQUA TECNICA

200

180

160

140

120

100

80

60

40

20

0

1,5 m2

4 m2

0

500

1000

1500

2000

2500

3000

Portata [l/h]

3500

4000

4500

5000

[

m

b

a

r

]

PRELIEVO ACS

ACCUMULO RISCALDATO SOLO NELLA PARTE INFERIORE

T acc.

45 °C

T prim.

10 °C

T prim.

T acc.

ACS PRELEVABILE [lt]

10 min

60 min

55 °C

50 °C

515

825

65 °C

60 °C

689

1143

70 °C

60 °C

720

1260

80 °C

60 °C

755

1415

PRELIEVO ACS

ACCUMULO RISCALDATO SOLO NELLA PARTE SUPERIORE

T acc.

45 °C

T prim.

T prim.

T acc.

ACS PRELEVABILE [lt]

10 min

60 min

55 °C

50 °C

208

560

65 °C

60 °C

296

720

70 °C

60 °C

328

960

80 °C

60 °C

364

1200

10 °C

www.dynergysrl.it

BOLLITORI, SERBATOI E CELLE TERMICHE 2023