PRESTAZIONI LINEA BOLLITORI
61
PRELIEVO ACS
MODELLO
SCAMBIATORI FISSI ACQUA TECNICA
INFERIORE
2,9 m2
MANDATA (NELLO SCAMBIATORE)
PORTATA
ΔT
T
2000 l/h
17
60 °C
2000 l/h
28
70 °C
2000 l/h
35
80° C
MANDATA (NELLO SCAMBIATORE)
PORTATA
ΔT
T
2000 l/h
30
60 °C
2000 l/h
48
70 °C
2000 l/h
60
80° C
ACCUMULO RISCALDATO SOLO NELLA PARTE INFERIORE
Prelievo ACS in continuo
10-45 °C
35 ΔT
POTENZA
PORTATA
41 kW
0,28 l/s
998 l/h
64 kW
0,44 l/s
1580 l/h
81 kW
0,55 l/s
1995 l/h
SUPERIORE
5 m2
Prelievo ACS in continuo
10-45 °C
35 ΔT
POTENZA
PORTATA
70 kW
0,48 l/s
1720 l/h
111 kW
0,76 l/s
2723 l/h
140 kW
0,96 l/s
3440 l/h
PERDITE DI CARICO SCAMBIATORI FISSI ACQUA TECNICA
250
200
150
100
50
0
2,9 m2
5 m2
0
500
1000
1500
2000
2500
3000
Portata [l/h]
3500
4000
4500
5000
[
m
b
a
r
]
T acc.
45 °C
T prim.
10 °C
T prim.
T acc.
ACS PRELEVABILE [lt]
10 min
60 min
55 °C
50 °C
1279
1935
65 °C
60 °C
1697
2708
70 °C
60 °C
1766
2980
80 °C
60 °C
1845
3325
PRELIEVO ACS
ACCUMULO RISCALDATO SOLO NELLA PARTE SUPERIORE
T acc.
45 °C
T prim.
T prim.
T acc.
ACS PRELEVABILE [lt]
10 min
60 min
55 °C
50 °C
495
1100
65 °C
60 °C
665
1400
70 °C
60 °C
720
1800
80 °C
60 °C
785
2200
10 °C
BOLLITORI, SERBATOI E CELLE TERMICHE 2023