AUS08
L SUBTOTAL
VOLUME
Daily tapping
volume l
The sum of the volume flow/flow
rate from the volume measure-
ment for the partial volume in l.
0...999.9
l
0
23:022
AUS09
CBM TOTAL
VOLUME
Daily tapping
volume m
3
The sum of the volume flow/flow
rate from the volume measure-
ment for the total volume in m
3
.
An exact reading can be taken
from the daily tapping volume in
l.
0...999.9
m
3
0
23:023
The visible values vary depending on the chosen
hydraulic variant and option and are dependent on
the code that is entered in the “Key” column.
Menu
Description
Range
Unit Key
ID
MENU
BAS
BASIS
BAS01
DHW
TEMP.SET-
POINT
Setpoint tem-
perature for
the fresh
water station
Setpoint temperature for the
domestic hot water preparation:
Value should be reached at TWW
and be maintained by the speed
control of the primary pump.
10...90
°C
0
05:051
BAS02
DHW TEMP.
MAXIMUM
Maximum
temperature
for the
domestic hot
water
Maximum permissible tempera-
ture on the secondary side.
Switch off the pump on the pri-
mary side if this is exceeded.
10
...90
°C
25
36:033
BAS03
TWW
SENSOR
TYPE
TWW
domestic hot
water sensor
selection,
sensor type
n 0: NTC 5K
n 1: PT 1000
n 2: 0...5 V
0...2
-
25
36:016
BAS04
TKW SENSOR
TYPE
TKW
domestic
cold water
sensor selec-
tion, sensor
type
n 0: NTC 5K
n 1: PT 1000
n 2: 0...5 V
0...2
-
25
36:017
03/2024 Item no. 215790 EA no. 1321