ES 5941Z

Info and menu parameters

NAC

RECHARGING

Adjuster is visible if RECHARGING PRIMARY NAC00 (08:100) is set to on.

NAC00

RECHARGING

PRIMARY

Option: Thermal recharging request (see above for

basic parameters)

on/off

off

NAC03

SWITCH ON

RECHARCHIN

G

Switch-on

hysteresis for

the tank set-

point tem-

perature

If the temperature in the tank is

> setpoint plus setting, a charging

request is ended.

1...30

K

08:063

NAC04

TO SENSOR

TYPE

TO tank top

sensor selec-

tion, sensor

type

n 0: NTC 5K

n 1: PT 1000

n 2: 0

...5 V

0 ...2

-

25

28:066

NAC09

RECHARGE

TIME PRO-

GRAM

Time program

for domestic

water

Time program for activating

domestic hot water preparation at

the normal setpoint or for acti-

vating recharging.

-

-

25

05:061

WHF

WARM

HOLDING

FUNCTION

Adjuster is visible if WARM HOLDING FUNCTION WHF00 (05:113) is set to on.

WHF00

WARM

HOLDING

FUNCTION

Option:

Standby/

warm holding

function

(see above for basic parameters)

on/off

off

25

05:113

WHF01

MIN SWITCH

OFF TIME

Min. switch

off time

The warm holding function is

blocked for the set time if the min-

imum switch-on time has elapsed or

if the flow temperature is reached.

0

...60

min.

25

36:040

WHF02

MAX

SWITCH ON

TIME

Min. switch

on time

The warm holding function is

switched off once the set time has

elapsed of if the flow temperature is

reached.

0

...30

min.

25

36:041

KOM

COMMUNI-

CATION

KOM01

LANGUAGE

SELECTION

0...8

-

0

04:056

KOM03

TOTAL

FAULT MES-

SAGE

Option: Fault

message

output

Here, the fault messages and info

messages are also diverted to the

output.

n -1: No voltage is output if

there is a total fault message

pending.

n 0: This function is not used.

n 1: Voltage is output if there is a

total fault message pending.

-1;0;1

0

25

08:111

32