Info and menu parameters

ES 5941Z

KOM04

EBUS

ADDRESS

eBUS address

Addressing of the controller in the

eBUS network

2...16

-

25

04:020

KOM05

EBUS

SUPPLY

Voltage supply for eBUS communi-

cation, max. load 180 mA.

on/off

-

25

04:036

STE

CONTROLS

STE11

TPV SENSOR

TYPE

TPV PWT pri-

mary flow

sensor selec-

tion, sensor

type

n 0: NTC 5K

n 1: PT 1000

0...1

-

25

28:027

STE12

MIN.RUN-

TIME TPV

PROTEC

Min. runtime

for primary

pump cycle/

protective

function

Is active if the temperature at

TPV falls below the value TPVset.

This serves to protect the heat

source from cooling down too

significantly. The value specifies

the minimum runtime/test time in

which the temperature is not per-

mitted to drop.

0...180

s

25

36:025

STE13

MIN.OFF-

TIME TPV

PROTEC

Waiting time

for the primary

pump cycle/

protective

function

Is active because TPV has fallen

below the value TPVset after

the minimum runtime; the pump

remains blocked for the setting.

This allows the heat source to

increase the temperature again.

0...60

min

25

36:026

MAN

MANUAL

Adjuster only has an effect if the operating mode selection is “Manual"

.

MAN01

SPEED PRIM.

PUMP

Manual value

output

Primary pump (FRIWA; PP)

0...100

%

0

08:088

MAN02

SPEED CIRC.

PUMP

Manual value

output

Circulation pump WWC

0...100

%

0

05:122

MAN03

RETURN

FLOW

SWITCH

Manual value

output

Return flow switch valve VSR

on/off

-

0

05:120

MAN04

CHECK

VALVE CAS-

CADE

Manual value

output

Cascade valve ZV

on/off

-

0

36:020

MAN05

RECHARGIN

G PRIMARY

Manual value

output

Recharging primary request

NACLAD

on/off

-

0

08:124

KAS

CASCADE

Adjuster only has an effect if OPERATING MODE STATION KAS01 (36:018) is set

> 0.

KAS01

OPERATING

MODE STA-

TION

Operating

mode of the

station:

n 0: Standalone

n 1: Slave

n 2: Master

0...2

-

25

36:018

03/2024 Item no. 215790 EA no. 1321