KOM04
EBUS
ADDRESS
eBUS address
Addressing of the controller in the
eBUS network
2...16
-
25
04:020
KOM05
EBUS
SUPPLY
Voltage supply for eBUS communi-
cation, max. load 180 mA.
on/off
-
25
04:036
STE
CONTROLS
STE11
TPV SENSOR
TYPE
TPV PWT pri-
mary flow
sensor selec-
tion, sensor
type
n 0: NTC 5K
n 1: PT 1000
0...1
-
25
28:027
STE12
MIN.RUN-
TIME TPV
PROTEC
Min. runtime
for primary
pump cycle/
protective
function
Is active if the temperature at
TPV falls below the value TPVset.
This serves to protect the heat
source from cooling down too
significantly. The value specifies
the minimum runtime/test time in
which the temperature is not per-
mitted to drop.
0...180
s
25
36:025
STE13
MIN.OFF-
TIME TPV
PROTEC
Waiting time
for the primary
pump cycle/
protective
function
Is active because TPV has fallen
below the value TPVset after
the minimum runtime; the pump
remains blocked for the setting.
This allows the heat source to
increase the temperature again.
0...60
min
25
36:026
MAN
MANUAL
Adjuster only has an effect if the operating mode selection is “Manual"
.
MAN01
SPEED PRIM.
PUMP
Manual value
output
Primary pump (FRIWA; PP)
0...100
%
0
08:088
MAN02
SPEED CIRC.
PUMP
Manual value
output
Circulation pump WWC
0...100
%
0
05:122
MAN03
RETURN
FLOW
SWITCH
Manual value
output
Return flow switch valve VSR
on/off
-
0
05:120
MAN04
CHECK
VALVE CAS-
CADE
Manual value
output
Cascade valve ZV
on/off
-
0
36:020
MAN05
RECHARGIN
G PRIMARY
Manual value
output
Recharging primary request
NACLAD
on/off
-
0
08:124
KAS
CASCADE
Adjuster only has an effect if OPERATING MODE STATION KAS01 (36:018) is set
KAS01
OPERATING
MODE STA-
TION
Operating
mode of the
station:
n 0: Standalone
n 1: Slave
n 2: Master
0...2
-
25
36:018
03/2024 Item no. 215790 EA no. 1321
33