TACOCONTROL Z1 S

Faults

Fault description

Cause

Remedy

Personnel

51 HTG setpoint unreached: Active

Heating supply temperature not reached for

3 minutes.

Setpoint reduction to actual value.

Control valve defec-

tive.

Replace the control

valve.

Heating and

sanitary techni-

cian

80 Input remote-off: Active

Remote off is active.

The entire control is inactive.

Heat interface unit

was switched off

externally.

Switch on the heat

interface unit again

using an external

signal.

Operator

Faults without an error message

The following sections describe faults that are not displayed on the

HMI, and how to repair them.

Fault description

Cause

Remedy

Personnel

Domestic hot water or heating

supply is cold.

Supply heat network

is cold.

Check the installation and values on

the HMI.

Operator

No flow on the pri-

mary side.

Check the installation and values on

the HMI. Proceed in the same way as

you would for the “No flow on the

primary side” fault, if necessary.

Heating and

sanitary techni-

cian

No flow on the primary side.

Strainer blocked.

Replace the strainer.

Heating and

sanitary techni-

cian

Valves closed or

defective.

Open or replace the valves.

Heating and

sanitary techni-

cian

Flow sensor is dirty

or defective.

Clean or replace the flow sensor.

Electrician

Prior installation

faulty.

Check the installation of the heat

interface unit.

Heating and

sanitary techni-

cian

Air in the system.

Remove the air from the system.

Heating and

sanitary techni-

cian

HMI does not display any infor-

mation about the heat inter-

face unit.

HMI not correctly

connected.

Reconnect the HMI (

Ä Chapter 6.1

‘Connecting the HMI’ on page 24).

Operator

HMI defective.

Replace the HMI. A new HMI can be

sourced from the supplier.

Operator

Circuit board defec-

tive.

Replace the circuit board ( Ä Chapter

9.4.2 ‘Replacing the circuit board’

on page 35).

Electrician

Internal wiring of

the LAN connection

faulty.

Open the controller and check the

wiring, and replace it, if necessary.

Electrician

34

Operating instructions

05/2024 Item no. 215251 EA no. EA-1291