TACOCONTROL Z1 S

Appendix for service personnel

Main overview ► Heating control

HMI text

Description

Value range

HTG supply tem-

perature

Supply temperature of the heating water

*Ctrl value HTG

valve

Control value for the control valve of the heating control

Setpoint HTG

supply

Setpoint for the supply temperature of the heating water

15 – 70 °C

*Input HTG

demand

Input signal from the room thermostat

Passive: No heat request

Active: Heat request

*Relay heating

pump

Signal at heating circulation pump

0%: No signal

100%: Pump activated

Main overview ► Heating control ►

Service settings Htg

HMI text

Description

Value range

*Max. HTG supply

temperature

Specifies the maximum temperature allowed in the heating supply. If this

value is exceeded in the heating supply, the valve for the heating supply

control closes and the circulation pump stops.

20 – 80 °C

*Min. dT Supply-

T_Htg

Minimum temperature difference allowed between the supply tempera-

ture from the heat network and the setpoint for the heating supply tem-

perature. If this temperature difference is not guaranteed, the setpoint is

reduced automatically.

0 – 10 °C

Main overview ► Functions primary side

HMI text

Description

Value range

Heat supply tem-

perature

Temperature of the water from the heat network

*Max. heat supply

temperature

Specifies the maximum temperature allowed in the heating supply.

50 – 100 °C

On level KWF

If the temperature on the primary side (supply from the heat network) falls

below this level, then the keep warm function is switched to active.

10 – 70 °C

Off level KWF

If the temperature on the primary side (supply from the heat network)

exceeds this level, then the keep warm function is deactivated.

10 – 70 °C

*Relay KW func-

tion

Signal for the keep warm function valve

Off: Valve closed

On: Valve open

*Input remote-off

Input signal from prepaid circuit

Passive: Contact open

Active: Contact closed

52

Operating instructions

05/2024 Item no. 215251 EA no. EA-1291