KESSEL AG
Catalogue EN 4.1
Wet installation, for outdoor underground installation
EN 12050-1
Tank volume: 1800 liters
Pump volume: max. 900 liters
Polyethylene system base (corrugated chamber)
for underground installation, resistant to aggressive
media. With Ø 160 mm inlet. For connection to
Ø 1000 mm system chamber.
Handles groundwater depths up to 3.000 mm.
With single or twin removable wastewater pump(s)
- with macerator (STZ)
- with multi-vane impeller (GTF)
- single-channel impeller (GTK)
for wastewater with or without sewage (without
ATEX requirements). With hydrostatic sensor for
level measurement. Pressure pipe Ø 90 mm
outside diameter (welded PE pipe is to be used
for the pressure pipe), including backflow
preventer and closure valve on pressure pipe side.
Power cable length: 10 m (30 m on request).
Control unit
With control unit with self-diagnosis system (SDS),
battery buffering and logbook function, control
unit is splashproof (IP 54).
Ø
1
8
8
0
1
4
0
0
Ø
1
6
0
1
3
2
0
1
0
9
0
Ø
9
0
1
7
3
5
2
1
6
0
2
4
4
0
P
u
m
p
i
n
g
s
t
a
t
i
o
n
s
Installation: in combination
with system chambers page 156 – 157
Accessories: pages 158 – 161
H [m]
4
60
50 2
40
3
1
30 6
20 5
10
1
STZ 4400-S1*
2
STZ 5200-S1*
3
STZ 7500-S1*
4
STZ 11000-S1*
5
GTF 5200-S1*
6
GTK 5200-S1*
Voltage
400 V
400 V
400 V
400 V
400 V
400 V
Amperage
7.5A
8.7A
13A
18.8 A
8.7A
8.7A
Input Power
(P1)
4.4 kW
5.2 kW
7.5kW
11 kW
5.2 kW
5.2 kW
Power (P2)
3.7kW
4.4 kW
6.4 kW
9.5 kW
4.4 kW
4.4 kW
Pumping
Pumping
capacity
height
10
20
30
Q [m
3
/h]
*Definition of S1-pumps see page 97
Ø 1000
1400
STZ pump
4400-S1
5200-S1
7500-S1
11000-S1
GTF pump
5200-S1
GTK pump
5200-S1
Pumping volume
in liters
820
820
820
820
Pumping volume
in liters
900
Pumping volume
in liters
900
Voltage
400 V
400 V
400 V
400 V
Voltage
400 V
Voltage
400 V
Art. no.
874 30 35
874 30 36
874 30 37
874 30 38
Art. no.
874 30 43
Art. no.
874 30 45
Art. no.
874 30 39
874 30 40
874 30 41
874 30 42
Art. no.
874 30 44
Art. no.
874 30 46
STZ pump
4400-S1
5200-S1
7500-S1
11000-S1
GTF pump
5200-S1
GTK pump
5200-S1
Pumping volume
in liters
800
800
800
800
Pumping volume
in liters
880
Pumping volume
in liters
880
Voltage
400 V
400 V
400 V
400 V
Voltage
400 V
Voltage
400 V
21.3 m
3
/h
21.3 m
3
/h
30.7 m
3
/h
30.6 m
3
/h
52.8 m
3
/h
51.6 m
3
/h
46.7 m
52 m
42 m
68 m
21 m
31.6 m